Viessmann · Boiler troubleshooting
Move and unpack boiler without carrying handles
What is going on
Use this method if the Viessmann carrying handles are not available. Avoid lifting or pushing against panels.
Check in this order
- Do not lift or position the boiler alone. Do not drop it or bump panels against the floor.
- Remove the top and sides of the crate, then lift the front panel up and out.
- Place a wooden block 12 in from the rear of the skid.
- Insert two 1 in Schedule 40 pipes through the openings in the casting legs and center them on the rear block.
- Lift the boiler on the pipes until it clears the skid, then remove the skid.
- Lower the boiler until the pipes rest on the front block.
- To remove the rear block, lift by the casting (not the jacket) to tilt the unit forward. To remove the front block, lift by the casting to tilt it backward.
- Remove the pipes and reinstall the front panel once the boiler is in place.
Applies to: VR1 22 to 33, 91 to 140
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 installation and service manual, p. 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.