Vent per the approved Category IV system and keep the termination clearances.
Check in this order
- Use only approved vent materials PVC/CPVC Schedule 40 or 80 solid core, approved polypropylene or approved stainless steel (USA).
- In Canada, use Type BH special gas vent Class IIA (PVC), IIB (CPVC) or IIC (polypropylene/stainless steel), certified to ULC-S636.
- Do not mix components from different vent system manufacturers.
- Keep at least 12 in above the highest anticipated snow level or grade for roof or vertical terminations (18 in in Canada).
- Keep at least 12 in clearance from any obstruction for the termination.
- Keep the vent within the maximum length and elbow limits in the venting table.
Applies to: NFB-301C/399C
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NFB-C quick installation guide, p. 3. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.