Convert the boiler from natural gas to propane

I-Series Plus

What is going on

The boiler is set up for natural gas only from the factory. Conversion must be done by a qualified service agency using the conversion kit instructions and local codes. Check the inlet gas pressure before you start.

Check in this order

  1. Confirm the inlet gas pressure is between the minimum and maximum allowed for this boiler.
  2. Shut off the gas supply before disconnecting electrical power.
  3. Locate the PC board (lower left of the unit) and the left PC board button.
  4. Press and hold the left PC board button for five seconds. 00-A appears.
  5. Scroll to parameter AO and press Select.
  6. Press the up or down arrow to choose the gas type, then press Select.
  7. Once the setting is complete, press the left PC board button to return to normal operation.
  8. Fit a new conversion label to the boiler showing the gas type.

Applies to: I-Series Plus condensing combi boiler

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai I-Series Plus IP060160C installation and operation manual, pp. 131-132. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.