Checking combustion quality (CO2 or O2 and CO)
What is going on
Test CO2 or O2 and CO at the lower and upper heating output. Allow about 50 seconds after start before testing, since the controller calibrates itself.
Likely causes
- CO2 or O2 outside the permissible range, which can point to a flue leak or a faulty ionization electrode or cable
Check in this order
- Connect a flue gas analyzer at flue gas port A on the boiler flue connection.
- Open the gas shut-off valve, start the boiler and create a call for heat.
- Set the lower heating output, then check CO2 and record it.
- Set the upper heating output, then check CO2. If it is more than 1% outside the range, correct it.
- Record the values, then re-seal test port A.
- If values are out of range, check the flue system for leaks (p. 49) and the ionization electrode and cable (p. 51).
- Check test port A for leaks. Escaping flue gas is harmful.
Applies to: Natural gas and LPG
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 59. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.