Viessmann · Boiler troubleshooting
Read ionization current through the burner control
What is going on
A multimeter cannot read ionization current. Use the burner control display sequence instead. The current should be at least 3 μA for 2 to 3 seconds after the gas valve opens and during operation.
Check in this order
- Press S F and hold for more than 2 seconds until the display area D flashes.
- Use Y E to set the service display to 5, then press S F so 5 shows in the status display.
- Use Y E to set the service display to .3, then press S F so 3 shows in the status display.
- Start the burner with the emissions test switch.
- Read the ionization current in the service display (for example 30 = 3.0 μA).
- Record the value on the maintenance record (page 64).
- Press S F and hold for more than 2 seconds, then use Y E to set the display to 5 and then 0.
- Press S F to return to the operating display.
Applies to: Vitocrossal 200 CM2 186 to 311
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.