Viessmann · Boiler troubleshooting

Read ionization current through the burner control

Vitocrossal 200 CM2

What is going on

A multimeter cannot read ionization current. Use the burner control display sequence instead. The current should be at least 3 μA for 2 to 3 seconds after the gas valve opens and during operation.

Check in this order

  1. Press S F and hold for more than 2 seconds until the display area D flashes.
  2. Use Y E to set the service display to 5, then press S F so 5 shows in the status display.
  3. Use Y E to set the service display to .3, then press S F so 3 shows in the status display.
  4. Start the burner with the emissions test switch.
  5. Read the ionization current in the service display (for example 30 = 3.0 μA).
  6. Record the value on the maintenance record (page 64).
  7. Press S F and hold for more than 2 seconds, then use Y E to set the display to 5 and then 0.
  8. Press S F to return to the operating display.

Applies to: Vitocrossal 200 CM2 186 to 311

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 17. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.