Viessmann · Boiler troubleshooting
Clean combustion chamber and heating surfaces
What is going on
Cleaning of the combustion chamber and heat exchanger surfaces. For CI2 1500 and 2000, clean both combustion chambers.
Check in this order
- Remove 3 cotter pins.
- Open and remove the inspection cover.
- Flush the combustion chamber and heating surfaces with water using a 90° angled pressure-washer nozzle.
- Apply cleaning agent and let it soak per the manufacturer's instructions.
- Use stainless-steel-safe cleaner; alkaline with surfactant for soot; slightly acidic chloride-free phosphoric-acid type for coatings and yellow-brown discoloration.
- Keep cleaning agent out between the boiler body and thermal insulation.
- Flush again until no cleaning agent residue remains; repeat if needed.
- Reassemble check the gasket, lubricate it with suitable paste, refit the cover and insert the cotter pins.
- Carry out a seal test (mirror or electrical sensor) after reassembly.
Applies to: Vitocrossal 200 CI2
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 service instructions, p. 31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.