Weil-McLain · Boiler troubleshooting
Display banner turned red
What is going on
A red banner means the control saw an error or a limit event. The home screen shows the fault name with a reset button.
Likely causes
- Control error or fault
- A limit circuit opened (internal high limit, external limit, LWCO)
Check in this order
- Write down the fault name shown on the home screen first.
- Open the contractor menu (hold the WM logo 7 seconds) > Diagnostics. It shows live readings and the lockout history.
- If a manual-reset limit tripped, find out why before you press reset. Resetting over and over hides the real problem.
- The full fault list and fixes are in the ECO Tec Boiler Manual (this Advanced Manual only covers settings).
- Normal banner colours for comparison blue = space heating call or maintenance reminder, purple = DHW call.
Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Control action, p.3; Homeowner menus p.55; Contractor menus p.57. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.