Viessmann · Boiler troubleshooting
Control calls for heat but burner does not respond
What is going on
The control is calling for heat but the burner or power venter does not run. Work through the burner, the power venter and the accessories.
Likely causes
- Burner is locked out or faulty
- Power venter has no separate 120 VAC supply to its motor
- Air proving switch, blower wheel or timer/relay in the power venter is defective
- Other accessory defect
- Fuse F1 has blown
Check in this order
- Reset the burner with the reset button under the burner hood.
- If the burner still does not respond, service it and see the troubleshooting section of the burner manual.
- Confirm the power venter has its own 120 VAC supply to the motor; see the power venter instructions.
- If the power venter still does not run, check the air proving switch, blower wheel and timer/relay per the power venter manual.
- Check all accessories operate properly and replace any that do not, using their supplied literature.
- If F1 has blown, replace it.
Applies to: Vitotronic 100 KW10B with burner and power venter
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100, KW10B Operating and User's Information manual, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.