Weil-McLain · Boiler troubleshooting

Limit controls and low water cutoff

SVF

What is going on

The control module has temperature-based high limit and operating limit control, certified to UL353 and ASME CSD-1 and Section IV. The operating limit set point equals supply maximum temperature plus the off differential. The control has two sets of limit contacts: one resets automatically and the other needs manual reset. Low-temperature circuits such as radiant slab should be protected by limits wired to a manual or automatic reset circuit. The low water cutoff is factory installed on the supply outlet pipe at the back of the heat exchanger, has a push-to-test button, and resets manually from the control display (MANUAL RESET).

Check in this order

  1. Set the operating limit to supply maximum temperature plus the off differential.
  2. Wire low-temperature circuits to a limit with manual or automatic reset, per page 49.
  3. Press the low water cutoff test button to check it.
  4. Reset a tripped low water cutoff through the display using MANUAL RESET.

Applies to: All SVF 1500-3000 models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 1500-3000 Series 1 boiler manual, p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.