Weil-McLain · Boiler troubleshooting
Check blower speeds at low fire, ignition and high fire
What is going on
Compares blower RPM with the altitude tables for the installed fuel and altitude.
Check in this order
- Above 2,000 ft, confirm the control is set up for the correct blower RPM for low fire and ignition.
- Navigate to Manual Control Firing Rate on the display (SVF Advanced Manual, part 550-100-207).
- Set the firing rate to 0% (low fire) and record the blower RPM.
- Compare the RPM with Table 18. It should not be below the minimum setting or above the ignition factory setting.
- Set the firing rate to 100% (high fire) and record the RPM.
- The high fire RPM should be within 200 RPM of the Table 18 value.
- If any value is outside these ranges, contact WM Technologies technical assistance.
Applies to: SVF 500/600 boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SVF 500/600 boiler manual, p. 116. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.