Check flame and combustion at high fire

SlimFit Series 2

What is going on

Force high fire, then check the flame and flue gas with calibrated instruments. The flame should be blue and stable, with orange dots over the burner surface.

Check in this order

  1. Call for heat from one of the heat demand inputs.
  2. Press and hold the UP and DOWN arrow keys for five seconds to open the installer menus.
  3. Go to DIAGNOSTICS and select Manual test mode, then force the rate to High.
  4. Look through the flame inspection window. The flame should be blue and stable, and the burner covered in orange dots.
  5. Remove the flue temperature sensor and insert the combustion probe.
  6. Measure CO2 (or O2) and CO. Compare against the acceptable values table.
  7. If values are not acceptable, follow the gas valve adjustment procedure.
  8. Reinstall the flue gas sample port cover, and reinstall the flue temperature sensor when finished.

Applies to: SlimFit Series 2 SF1000, SF1500, SF2000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 82. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.