Viessmann · Boiler troubleshooting

Checking the outside temperature sensor

Vitodens 222-F

What is going on

Sensor type is NTC 10 kΩ. Compare the measured resistance with the temperature curve. Resistance curve values are in a chart that is not readable in the text.

Check in this order

  1. Pull plug X3 from the control unit.
  2. Measure resistance across terminals X3.1 and X3.2 on the disconnected plug and compare it with the curve.
  3. If values deviate severely, disconnect the wires at the sensor and test the sensor itself.
  4. Replace the lead or the outside temperature sensor, depending on the result.

Applies to: Vitodens 222-F B2TB

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 222-F B2TB service instructions, p. 82. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.