Viessmann · Boiler troubleshooting
Checking the outside temperature sensor
What is going on
Sensor type is NTC 10 kΩ. Compare the measured resistance with the temperature curve. Resistance curve values are in a chart that is not readable in the text.
Check in this order
- Pull plug X3 from the control unit.
- Measure resistance across terminals X3.1 and X3.2 on the disconnected plug and compare it with the curve.
- If values deviate severely, disconnect the wires at the sensor and test the sensor itself.
- Replace the lead or the outside temperature sensor, depending on the result.
Applies to: Vitodens 222-F B2TB
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 222-F B2TB service instructions, p. 82. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.