Weil-McLain · Boiler troubleshooting

Zoning: four space heating zones, no indirect DHW

SVF 500/600 Series 1

What is going on

Each of the four input and output pairs runs one heating zone with its own thermostat and circulator or zone valve.

Check in this order

  1. Wire the zone thermostats to Input 1 (J17 1 and 2), Input 2 (J17 4 and 5), Input 3 (J17 7 and 8) and Input 4 (J16 1 and 2).
  2. Wire circulators or 120 Vac zone valves to Outputs 1 to 4 as shown in the zoning diagram.
  3. Choose the space heating system type during the Wizard, or set it manually in the PRIORITY 2 menu of System Settings.
  4. Keep the factory default settings for the chosen system type, or change them if needed.

Applies to: SVF 500/600 Series 1 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 Series 1 boiler manual 550-100-273/1224, p. 80. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.