Additional high temperature limit in ASME systems
What is going on
ASME installations may need a manual reset high temperature limit in the supply piping between the boiler and its isolation valve. Its setting must stay below 240°F. The Unity CI control shuts the boiler down at 210°F, or lower if set lower.
Check in this order
- Where ASME applies, install a manual reset high temperature limit in supply piping between the boiler and isolation valve.
- Set the external limit below 240°F.
- Confirm the Unity CI operating limit (210°F or lower) is the boiler shutdown point.
- Check local codes for other requirements.
Applies to: CGi Series 5 boilers with Unity CI control
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 gas-fired water boiler manual, p. 43. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.