Weil-McLain · Boiler troubleshooting

Additional high temperature limit in ASME systems

CGi Series 5

What is going on

ASME installations may need a manual reset high temperature limit in the supply piping between the boiler and its isolation valve. Its setting must stay below 240°F. The Unity CI control shuts the boiler down at 210°F, or lower if set lower.

Check in this order

  1. Where ASME applies, install a manual reset high temperature limit in supply piping between the boiler and isolation valve.
  2. Set the external limit below 240°F.
  3. Confirm the Unity CI operating limit (210°F or lower) is the boiler shutdown point.
  4. Check local codes for other requirements.

Applies to: CGi Series 5 boilers with Unity CI control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: CGi Series 5 gas-fired water boiler manual, p. 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.