Weil-McLain · Boiler troubleshooting
Ultra-80 or Ultra-105 low output on 2-inch vent/air pipe
What is going on
The Ultra-80 and 105 allow 2-inch PVC vent and air pipe, but the boiler derates itself because of the extra pressure drop. Lower output is expected, not a fault.
Likely causes
- 2-inch vent and air pipe used on Ultra-80 or 105
- Long equivalent length or too many elbows
Check in this order
- Check pipe size and total equivalent length. Max is 100 equivalent feet with the elbow limits in the guide.
- Count elbows 7 ft each for 2 or 3 in. long-radius 90 or 45 elbows and 4 in. elbows; 16 ft each for 2 or 3 in. short-radius elbows.
- With 2-inch pipe at 100 ft, expect up to about 10% derate on the Ultra-80 and 15% on the Ultra-105.
- If the house needs full output, re-pipe in 3-inch (reducers per the guide).
- Concentric terminations PVC schedule 40 only, no CPVC or ABS.
Applies to: Weil-McLain Ultra-80 and Ultra-105 Series 3 gas boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain Ultra Series 3 Quick-Start installation guide and material checklists C-1120 (0910), vent/air piping length table. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.