Ultra-80 or Ultra-105 low output on 2-inch vent/air pipe

Ultra Series 3

What is going on

The Ultra-80 and 105 allow 2-inch PVC vent and air pipe, but the boiler derates itself because of the extra pressure drop. Lower output is expected, not a fault.

Likely causes

  • 2-inch vent and air pipe used on Ultra-80 or 105
  • Long equivalent length or too many elbows

Check in this order

  1. Check pipe size and total equivalent length. Max is 100 equivalent feet with the elbow limits in the guide.
  2. Count elbows 7 ft each for 2 or 3 in. long-radius 90 or 45 elbows and 4 in. elbows; 16 ft each for 2 or 3 in. short-radius elbows.
  3. With 2-inch pipe at 100 ft, expect up to about 10% derate on the Ultra-80 and 15% on the Ultra-105.
  4. If the house needs full output, re-pipe in 3-inch (reducers per the guide).
  5. Concentric terminations PVC schedule 40 only, no CPVC or ABS.

Applies to: Weil-McLain Ultra-80 and Ultra-105 Series 3 gas boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 3 Quick-Start installation guide and material checklists C-1120 (0910), vent/air piping length table. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.