Louver sizing for combustion air openings
What is going on
If the free area of louvers is unknown, assume 20% free area for wood and 60-75% for metal louvers. Openings must be made larger to allow for louver restriction. Example: a free 14 in x 6 in (356 x 152 mm) opening becomes 14 in x 10 in (356 x 254 mm) with metal louvers.
Check in this order
- Find the free area of the louver from the maker.
- If unknown, assume 20% for wood louvers.
- If unknown, assume 60-75% for metal louvers.
- Enlarge the opening so the free area is met after the louver.
Applies to: Closet combustion air openings
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 Installation Instructions, p. 55. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.