NX burner: cad cell resistance check
What is going on
The NX has a small air tube and a throttle cup with small sight windows, so less light reaches the cad cell and the reading is often higher than on older burners. Check it before blaming the control.
Likely causes
- Dirty cad cell lens
- Soot or oil film on the throttle cup sight windows
- Damaged or scratched sight window
- Cad cell going bad
Check in this order
- Read the resistance with flame on GeniSys display module 52067U or Contractor Tool 52082U, or unplug the cad cell leads at the control and use a meter.
- 0 to 1600 ohms with flame is normal. From 1600 ohms up to the lockout point is the limited range: clean or fix before it starts locking out.
- Power off. Clean the cad cell lens.
- Clean the throttle cup sight windows with a soft cloth and degreaser. Do not scratch, puncture or remove them. If a window is damaged, replace the nozzle line assembly with one that has a windowed throttle cup.
- Recheck the reading with the burner cover installed.
Applies to: Beckett NX burner with GeniSys 7505 primary control on Weil-McLain Ultra Oil UO-3, UO-4, UO-5 (CV and DV)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Beckett NX Burner Manual for Weil-McLain Ultra Oil boilers (W-M 550-141-996/0321), Cad cell resistance indicator p.12; cad cell note p.15; maintenance p.17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.