Rinnai · Boiler troubleshooting
Venting slope and pressure plane rules
What is going on
Slope rules for horizontal venting and rules against mixing vent pressure planes or sharing pipes.
Likely causes
- Venting in different pressure planes can cause poor boiler performance.
Check in this order
- Do not install the boiler with venting in different pressure planes.
- Slope horizontal exhaust 1/4 in per foot (about 2 cm per metre) toward the boiler.
- Do not slope the combustion air pipe toward the boiler.
- Do not bring exhaust and combustion air together into a single PVC pipe with a fitting.
- Do not common-vent with another manufacturer's induced draft appliance.
Applies to: Horizontal and multi-pipe venting
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 38. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.