Heating system design version 4: return temperature control with three-way mixing valve
What is going on
Multi-boiler cascade with a Vitocontrol-S controlling Vitotronic 100 GC1 boiler controls via LON. Used for older heating systems, systems in nurseries, or systems where downstream heating circuits cannot be controlled. Sensor T1 closes the three-way mixing valve in proportion to protect the boiler when the required minimum return temperature is not reached.
Check in this order
- Set the coding listed in the system version 4 coding table on every Vitotronic 100 GC1.
- Set the Vitocontrol-S coding as listed in the same table.
- Connect temperature sensor T1 to plug aJA.
- Size each boiler circuit pump so its volume flow is at least the maximum total heating circuit volume flow (recommendation: 110%).
- Check the connection diagram on site for completeness and function. Single-phase and three-phase pumps need field-supplied motor contactors or starters.
Applies to: Heating system design version 4 (Vitotronic 100 GC1 with Vitocontrol-S VD2/CT3/CM2)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.