Viessmann · Boiler troubleshooting

Heating system design version 4: return temperature control with three-way mixing valve

Vitotronic 100 GC1Vitocontrol-S VD2/CT3/CM2

What is going on

Multi-boiler cascade with a Vitocontrol-S controlling Vitotronic 100 GC1 boiler controls via LON. Used for older heating systems, systems in nurseries, or systems where downstream heating circuits cannot be controlled. Sensor T1 closes the three-way mixing valve in proportion to protect the boiler when the required minimum return temperature is not reached.

Check in this order

  1. Set the coding listed in the system version 4 coding table on every Vitotronic 100 GC1.
  2. Set the Vitocontrol-S coding as listed in the same table.
  3. Connect temperature sensor T1 to plug aJA.
  4. Size each boiler circuit pump so its volume flow is at least the maximum total heating circuit volume flow (recommendation: 110%).
  5. Check the connection diagram on site for completeness and function. Single-phase and three-phase pumps need field-supplied motor contactors or starters.

Applies to: Heating system design version 4 (Vitotronic 100 GC1 with Vitocontrol-S VD2/CT3/CM2)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 GC1 / Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.