INT boiler disable interlock wiring

Versatronik 300 Cascade Control

What is going on

The INT input takes a potential-free dry contact. The plant shuts down when the contact is open. Closing the contact allows operation.

Check in this order

  1. Wire the BMS or mechanical control (damper or blower motor) through a field-supplied relay to the INT terminals.
  2. Use an AC or DC relay coil with the correct control voltage. The contact must close for the boiler plant to run.
  3. Use low-voltage wiring and keep it away from 120/240 VAC conductors.

Applies to: INT terminals

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Versatronik 300 Cascade Control technical, installation and configuration manual, p. 10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.