Navien · Boiler troubleshooting
Cascade system roles and operating rules
What is going on
Cascade system with one NCB700 combi-boiler and up to 15 Navien NPE-A2 or NPE-S2 water heaters.
Check in this order
- Set the NCB700 as the main unit. It controls the on/off state of all sub units.
- Set each NPE sub unit to DHW only. Only the main unit provides space heating.
- Make all setting changes at the main unit. Changes made on sub units are ignored.
- Configure each unit for cascade operation.
- After saving cascade settings, turn the boiler and all water heaters off, then back on for the changes to take effect.
- Sub units start in stages to meet DHW demand once the main unit turns them on.
- If an error occurs in a cascade, the error shows on the display of the unit that failed.
Applies to: NCB700 main unit with NPE-A2 or NPE-S2 sub units
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Navien NCB700 installation and operation manual, p. 83. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.