Heating circuit behaviour during DHW tank heating (priority settings)

Vitocrossal 300 CA3B Dual Fuel

What is going on

How the heating circuits react while the DHW tank is being heated depends on the priority setting. Priority is set at coding a2 in the Heating circuit group.

Check in this order

  1. With priority control (coding a2:2): the heating circuit set supply temperature drops to 32°F (0°C) during tank heating, the mixing valve closes and the heating circuit pump is switched off.
  2. Without priority control the heating circuit keeps running at the same set value.
  3. With modulating priority and mixing valve circuits: the heating circuit pump stays on and the set supply temperature is reduced until the set boiler water temperature is reached. The reduction is based on outdoor temperature, boiler water difference, heating curve slope and shift, and coding a2.

Applies to: Heating circuits with DHW priority

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel service instructions, p. 40 and p. 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.