Viessmann · Boiler troubleshooting
Check the flue gas temperature sensor (VD2/VD2A/CT3 only)
What is going on
Monitors flue gas temperature against a selected limit. Plugs into socket 15.
Check in this order
- Disconnect plug aG in the terminal compartment.
- Measure resistance at terminals 1 and 2 of the plug.
- Compare the reading with the actual flue gas temperature using the resistance table.
- If the value differs significantly, check installation and replace the sensor if needed.
- Plug the sensor into socket 15 on the boiler control.
Applies to: Flue gas temperature sensor, socket 15, VD2/VD2A/CT3 only
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 Installation and Service Instructions, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.