Viessmann · Boiler troubleshooting

Check the flue gas temperature sensor (VD2/VD2A/CT3 only)

Vitotronic 300

What is going on

Monitors flue gas temperature against a selected limit. Plugs into socket 15.

Check in this order

  1. Disconnect plug aG in the terminal compartment.
  2. Measure resistance at terminals 1 and 2 of the plug.
  3. Compare the reading with the actual flue gas temperature using the resistance table.
  4. If the value differs significantly, check installation and replace the sensor if needed.
  5. Plug the sensor into socket 15 on the boiler control.

Applies to: Flue gas temperature sensor, socket 15, VD2/VD2A/CT3 only

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 Installation and Service Instructions, p. 29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.