Viessmann · Boiler troubleshooting

Maximum boiler water temperature and mixing valves

Vitocrossal 300 CU3A

What is going on

Maximum boiler water temperature for space heating and DHW is 194°F (90°C). Use a maximum boiler supply of 194°F (90°C) to reduce distribution losses. Avoid mixing valves to keep return temperatures low for condensing. If a mixing valve is needed, use only 3-way mixing valves. Never use 4-way mixing valves with condensing boilers.

Check in this order

  1. Set the maximum boiler supply temperature to 194°F (90°C).
  2. Avoid mixing valves where possible.
  3. If a mixing valve is required, use a 3-way valve only.
  4. Do not use 4-way mixing valves.

Applies to: Vitocrossal 300 CU3A

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CU3A application guide, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.