Weil-McLain · Boiler troubleshooting

Install condensate trap and drain line

ECO Tec Series 3

What is going on

The condensate trap, hose clamp and drain line must be in place during all operation. Condensate is slightly acidic (pH about 3.2 to 4.5), so use a neutralizing filter when draining into metal pipe if codes require it.

Likely causes

  • Frozen or obstructed condensate line, which can push condensate out of the boiler tee and cause water damage

Check in this order

  1. Remove the pedestal front access panel if the boiler is floor standing.
  2. Assemble the flexible drain tube with the nut and gasket ring, with the tube extending about ¼" through the gasket.
  3. Seat the gasket offset edge on the drain fitting shoulder and finger-tighten the nut.
  4. Slide the hose clamp onto the condensate outlet tube.
  5. Slide the trap assembly into the condensate outlet tube and tighten the hose clamp.
  6. On floor standing boilers, route the hose through the slot in the pedestal side.
  7. Run at least ½" PVC to a floor drain or condensate pump, using a ¾" PVC coupling at the flexible line.
  8. Use materials approved by the authority having jurisdiction. Without other authority, PVC and CPVC must meet ASTM D1785, F441 or D2665, and cement and primer must meet ASTM D2564 or F493. In Canada use CSA or ULC certified PVC or CPVC.

Applies to: ECO Tec Series 3 condensate outlet

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 boiler manual, p. 63. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.