Weil-McLain · Boiler troubleshooting

Check temperature sensors (resistance test)

SlimFit Series 2

What is going on

Sensors are resistance type. Compare measured ohms to the tables at known temperatures.

Likely causes

  • Sensor out of range
  • Control misreading temperature

Check in this order

  1. Measure the sensor resistance at a known temperature: 32 °F ice water, room temperature (about 60 to 70 °F), or 212 °F boiling water.
  2. Compare the reading with the sensor resistance tables in this section for the matching sensor type.
  3. To check whether the control reads correctly, connect a resistance decade box in place of the sensor and compare the displayed temperature with the value for that resistance.

Applies to: SlimFit 1000-2000 MBH Series 2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 94. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.