Weil-McLain · Boiler troubleshooting
Check temperature sensors (resistance test)
What is going on
Sensors are resistance type. Compare measured ohms to the tables at known temperatures.
Likely causes
- Sensor out of range
- Control misreading temperature
Check in this order
- Measure the sensor resistance at a known temperature: 32 °F ice water, room temperature (about 60 to 70 °F), or 212 °F boiling water.
- Compare the reading with the sensor resistance tables in this section for the matching sensor type.
- To check whether the control reads correctly, connect a resistance decade box in place of the sensor and compare the displayed temperature with the value for that resistance.
Applies to: SlimFit 1000-2000 MBH Series 2
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 boiler manual 550-100-561/1225, p. 94. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.