Viessmann · Boiler troubleshooting
Connect gas supply and manual shutoff
What is going on
Gas piping must be sized for the full connected load of the home, with no noticeable pressure drop when any appliance lights or runs. Piping must not block access to serviceable parts.
Check in this order
- Size the gas pipe from run length, number of fittings, gas type and total input of all gas appliances, using CAN/CSA B149.1 and .2 or NFPA 54 plus local codes.
- Install a ground joint union, a capped drip leg and a listed manual shutoff valve ahead of the boiler.
- Connect the gas line to the boiler gas connection.
- Leave the manual shutoff valve closed after connection, then test the piping as described in the pressure test guide.
- Tag the shutoff valves and show the owner where they are.
- For LPG installs below ground level, fit an external safety solenoid valve and set the system coding per the Service Instructions.
Applies to: Vitodens 200-W B2HB gas connection
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HB installation manual, p. 18-19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.