Piping layout: direct-connected heating circuit plus one system-separated circuit

Vitodens 200-W B2HB

What is going on

Boiler with one direct-connected heating circuit and one circuit separated by a plate heat exchanger, with DHW storage. The radiator circuit runs off the boiler pump, and the under-floor circuit is held to a lower temperature by a 3-way mixing valve.

Check in this order

  1. Confirm the combined flow of both heating circuits stays below the boiler's maximum water flow rate (see the boiler flow table on page 10).
  2. If the application flow may exceed the boiler maximum, or the system flow is unknown, install a low-loss header. It is an accessory.
  3. Size the plate heat exchanger so its secondary-side pressure drop is no more than the pressure drop of the 3-way mixing valve.
  4. Let the boiler pump supply the radiator circuit and the plate heat exchanger.
  5. Pipe the DHW recirculation pump so it pumps into the boiler.
  6. Run the mixing valve for the under-floor circuit through the accessory mixing-valve kit.

Applies to: Vitodens 200-W B2HB boiler with Vitotronic 200, HO1B outdoor reset control

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.