Piping layout: direct-connected heating circuit plus one system-separated circuit
What is going on
Boiler with one direct-connected heating circuit and one circuit separated by a plate heat exchanger, with DHW storage. The radiator circuit runs off the boiler pump, and the under-floor circuit is held to a lower temperature by a 3-way mixing valve.
Check in this order
- Confirm the combined flow of both heating circuits stays below the boiler's maximum water flow rate (see the boiler flow table on page 10).
- If the application flow may exceed the boiler maximum, or the system flow is unknown, install a low-loss header. It is an accessory.
- Size the plate heat exchanger so its secondary-side pressure drop is no more than the pressure drop of the 3-way mixing valve.
- Let the boiler pump supply the radiator circuit and the plate heat exchanger.
- Pipe the DHW recirculation pump so it pumps into the boiler.
- Run the mixing valve for the under-floor circuit through the accessory mixing-valve kit.
Applies to: Vitodens 200-W B2HB boiler with Vitotronic 200, HO1B outdoor reset control
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HB technical data manual, p. 40. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.