Viessmann · Boiler troubleshooting

Replace gas valve (natural gas)

Vitocrossal 200 CM2

What is going on

Remove and replace the NG gas valve on the manifold, then leak test.

Check in this order

  1. Disconnect the black plug from the gas valve and remove its screw.
  2. Disconnect the white plug marked GDW2 from the gas pressure switch and remove its screw.
  3. Disconnect the white plug from the gas pressure switch and remove its screw.
  4. Remove the four M5 (4 mm hex) screws from the lower gas valve flange and set them aside.
  5. Disconnect the gas supply line.
  6. Disconnect the compensation tubing from the gas valve.
  7. Remove the tube support and set it aside.
  8. Remove the four M5 (8 mm hex) nuts from the gas manifold and set them aside.
  9. Clean the manifold surface and replace the O-ring.
  10. Fit the new gas valve, installing M5 studs and torquing them as specified.
  11. Reinstall in reverse order and torque the fasteners.
  12. Leak test all reconnected gas line and valve connections.

Applies to: Gas valve for natural gas

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.