Replace gas valve (natural gas)
What is going on
Remove and replace the NG gas valve on the manifold, then leak test.
Check in this order
- Disconnect the black plug from the gas valve and remove its screw.
- Disconnect the white plug marked GDW2 from the gas pressure switch and remove its screw.
- Disconnect the white plug from the gas pressure switch and remove its screw.
- Remove the four M5 (4 mm hex) screws from the lower gas valve flange and set them aside.
- Disconnect the gas supply line.
- Disconnect the compensation tubing from the gas valve.
- Remove the tube support and set it aside.
- Remove the four M5 (8 mm hex) nuts from the gas manifold and set them aside.
- Clean the manifold surface and replace the O-ring.
- Fit the new gas valve, installing M5 studs and torquing them as specified.
- Reinstall in reverse order and torque the fasteners.
- Leak test all reconnected gas line and valve connections.
Applies to: Gas valve for natural gas
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.