Viessmann · Boiler troubleshooting
Testing the flow switches / flow sensors
What is going on
Both flow sensing devices shut the burner down on low flow and block restart until flow is restored. The test is done by throttling the water flow to or from the boiler; the boiler should shut down once flow drops below its safe set point.
Check in this order
- Throttle the water flow to or from the boiler.
- Confirm the boiler shuts down when flow drops below the safe operating set point.
- Restore full flow and confirm the burner can restart.
Applies to: Models 112, 150, 399, 530
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.