Weil-McLain · Boiler troubleshooting
Direct exhaust conversion and combustion air openings
What is going on
Direct exhaust conversion requires the Weil-McLain Direct Exhaust Venting Kit. Boiler room combustion air openings must be sized for all appliances in the room, including the ECO Tec BTU rating. Openings are sized per the manual figure. Negative pressure from exhaust fans or other mechanical ventilation can defeat the openings.
Likely causes
- Boiler room under negative pressure from exhaust fans or mechanical ventilation
- Other appliances in the room not counted in air sizing
Check in this order
- Use the Direct Exhaust Venting Kit to convert the boiler to direct exhaust.
- Follow both this manual and the Direct Exhaust Venting Kit instructions.
- Install 3 in PVC or CPVC pipe and elbow on the boiler air inlet and a 3 in screen in the elbow opening.
- Use the template to cut only the exhaust hole in the wall.
- Add the ECO Tec BTU rating to the room total with all other appliances when sizing air openings.
- Check that the room is not under negative pressure.
Applies to: Direct exhaust option, all 80/110/150/199
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Boiler Manual, p. 45. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.