Weil-McLain · Boiler troubleshooting

Route condensate drain tubing

Ultra Series 4

What is going on

The drain line must stay open and unobstructed. A frozen or blocked line can spill condensate and cause water damage.

Likely causes

  • Condensate freezes in the line
  • Line is obstructed

Check in this order

  1. Connect the drain tubing to the 1/2 in PVC tee and run it to a floor drain or condensate pump.
  2. Use 1/2 in PVC or CPVC, or 5/8 in I.D. tubing, and use materials approved locally. In Canada, use CSA or ULC certified pipe and fittings.
  3. Leave the top of the 1/2 in tee open as a vacuum break.
  4. If using a pump, choose one approved for condensing boilers and furnaces, with an overflow switch.
  5. When sizing the pump, include the total load of all Ultra boilers connected to it.

Applies to: All Ultra models

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 4 boiler manual, p. 28. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.