Weil-McLain · Boiler troubleshooting
Gas valve leakage testing
What is going on
Test each gas valve solenoid on its own. Do not connect a manometer to either gas valve.
Check in this order
- Do not connect a manometer to the manual or automatic gas valve; blower vacuum can draw fluid into the gas line.
- Follow the gas valve manufacturer's leak test procedure.
- Open the Gas Valve Test Screen from the control menu (see page 71).
- Highlight Open Gas Valve 1 and press enter/save.
- Give the boiler a call for heat. Only gas valve 1 opens.
- After gas valve 1 opens, end the call for heat.
- Repeat for Open Gas Valve 2.
- Exit with the back button to restore both valves for normal calls for heat.
Applies to: SVF 1500-3000
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF Series 1 boiler manual, p. 90. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.