Weil-McLain · Boiler troubleshooting

Gas valve leakage testing

SVF Series 1

What is going on

Test each gas valve solenoid on its own. Do not connect a manometer to either gas valve.

Check in this order

  1. Do not connect a manometer to the manual or automatic gas valve; blower vacuum can draw fluid into the gas line.
  2. Follow the gas valve manufacturer's leak test procedure.
  3. Open the Gas Valve Test Screen from the control menu (see page 71).
  4. Highlight Open Gas Valve 1 and press enter/save.
  5. Give the boiler a call for heat. Only gas valve 1 opens.
  6. After gas valve 1 opens, end the call for heat.
  7. Repeat for Open Gas Valve 2.
  8. Exit with the back button to restore both valves for normal calls for heat.

Applies to: SVF 1500-3000

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 boiler manual, p. 90. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.