Weil-McLain · Boiler troubleshooting
Wizard setup order
What is going on
The Wizard leads through boiler settings, inputs and outputs, priorities, system settings and types, output activation, priority switching, date and time, and installer information. Altitude must be set correctly and WWSD is set to the outdoor temperature above which space heating stops.
Check in this order
- Boiler Settings set altitude and WWSD.
- Inputs/Outputs select the use of inputs 1, 2 and 3, and the outputs that match them.
- Set Priorities assign priorities 1, 2 and 3 to the inputs.
- System Settings and System Types set the system settings, and choose the system type on each output.
- Output Activation choose when AUX PUMP/OUTPUT turns on, if used.
- Priority Switching set max and min timings.
- Date/Time set the clock, which is used for diagnostic logging.
- Information enter installer contact, CP#, install and maintenance dates, and maintenance notice timing.
Applies to: SF1000L/R, SF1500L/R, SF2000L/R
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 2 Boiler Manual 550-100-561/1225, p. 63. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.