Combustion air contamination check before piping air or openings
What is going on
Corrosive vapours and dust can enter combustion air and damage the burner and heat exchanger. Keep intake areas and boiler room clean.
Likely causes
- Chloro/fluorocarbon spray cans, permanent wave solutions, chlorinated cleaners or waxes
- Chlorine pool chemicals, calcium chloride, sodium chloride used for softening
- Refrigerant leaks, paint or varnish removers, hydrochloric/muriatic acid
- Cements, glues and adhesives, antistatic dryer softeners, chlorine bleaches and laundry solvents
- Excessive dust and dirt
- Dry cleaning, pool, metal fabrication, beauty shop, refrigeration repair, photo processing, auto body, plastic manufacturing, furniture refinishing, new construction, remodeling and garage workshop areas
Check in this order
- Direct exhaust provide combustion air openings to the boiler room per this manual, and confirm the room and source air are free of contaminants.
- Direct vent run the air inlet piping per this manual and do not terminate it where contaminated air can be drawn in.
- Check the Figure 12 list of products and areas before choosing the air intake location.
- If the boiler shares a space with other appliances, size the air openings for the combined load.
Applies to: SF-550 and SF-750
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 3 boiler manual 550-100-559/0725, pp. 21-22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.