Weil-McLain · Boiler troubleshooting

Ultra Series 3 short cycling or poor heat: check primary/secondary piping

Ultra Series 3

What is going on

The Ultra must sit on its own boiler loop, piped primary/secondary. Wrong tee connections or undersized loop pipe cause flow problems.

Likely causes

  • Boiler loop connected to the run of the tees instead of the branch
  • Primary/secondary tees more than 12 in. apart
  • Boiler loop pipe smaller than the minimum
  • Boiler circulator used for the system instead of the boiler loop

Check in this order

  1. The boiler loop must enter the tees through the branch connection, never the straight-through run.
  2. Keep the two system tees no more than 12 in. apart.
  3. Boiler loop minimum pipe size Ultra-80/105 1 in.; Ultra-155/230 1-1/4 in.; Ultra-299/399 1-1/2 in.
  4. The circulator shipped with the boiler is only for the boiler loop. System, zone and DHW circulators are supplied by the installer.
  5. Optional Easy-Up manifolds 383-500-649 (1-1/4 in., Ultra-80/105) and 383-500-661 (1-1/2 in., Ultra-155 to 399).

Applies to: Weil-McLain Ultra Series 3 gas boilers (Ultra-80 to Ultra-399)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 3 Quick-Start installation guide and material checklists C-1120 (0910), water piping panel. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.