Viessmann · Boiler troubleshooting

Low water cut-off (LWCO) connection, VD2/VD2A/CT3

Vitotronic 300

What is going on

Wiring of an external low water cut-off device. The factory jumper must be removed before the device is connected in series.

Check in this order

  1. Remove the jumper between terminals 12 and 15.
  2. Connect the LWCO device as shown in the diagram.
  3. Refer to the LWCO manual for its exact interconnection.

Applies to: VD2/VD2A/CT3 controls

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 300 GW2 installation and service instructions, p. 49. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.