Viessmann · Boiler troubleshooting
Annual service by heating contractor
What is going on
Performed by a qualified heating contractor or service agency at least once a year.
Likely causes
- Deficiencies not corrected in time
- Leaks in pipe joints, valves or air vents
- Chemicals or combustibles stored too close to the boiler
Check in this order
- Test the safety high limits and the burner with its accessories.
- Test and establish proper chemical makeup of system water.
- Check flue pipe, chimney connection and chimney.
- Check the pressure relief valve, system pressure and automatic feed if fitted.
- Check heating pipe joints, valves and air vents; repair leaks immediately.
- Check combustion air and ventilation to the boiler and mechanical room.
- Test the high limits by lowering settings and cycling the burner.
- Test the low water cut-off and check per the manufacturer's instructions; flush float types.
- Check lubrication of field-installed circulating pumps per manufacturer.
- On oil check fuel lines are tight; clean or replace fuel filters annually; inspect the oil tank.
- On gas check gas piping, unions, gas valve and manifold for gas tightness.
- Check ignition and operation of the oil or gas burner.
- Perform a combustion test.
- Check the door safety switch and the low water cut-off.
- Inspect the low and/or high pressure gas switch if fitted.
- Inspect the main burner flame and follow the burner maker's service instructions.
- Keep the boiler room free of dust, humidity, aggressive vapours and chlorine chemicals.
- Retighten or reseal the combustion chamber door, clean-out covers, fiber rope seals and flanges as needed.
Applies to: All VD2 sizes 320 to 1080
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.