Viessmann · Boiler troubleshooting
Connecting 120V external pumps
What is going on
Pump wiring depends on the pump's electrical draw and voltage. Larger pumps and non-120V pumps need a field-supplied contactor or relay.
Check in this order
- For 120V pumps drawing more than 2 FLA, use a field-supplied contactor or relay rated 120VAC 1A.
- For 208/460/575V 3-phase pumps, use a field-supplied contactor or relay rated 120VAC 1A.
- For 240V pumps, use a field-supplied contactor or relay rated 120VAC 1A.
- Feed the contactor from a power supply with disconnect and protection.
- For 120V pumps drawing less than 2 FLA, wire the pump directly to the DIN rail.
Applies to: Vitotronic 200-H HK1B, external pump connections
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200-H, HK1B Installation and Service Instructions, p. 18. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.