Weil-McLain · Boiler troubleshooting
Category II draft control devices
What is going on
Because the SlimFit runs cooler flue gas, it may not create enough draft. Add draft control and safety devices as recommended to keep negative pressure in range.
Likely causes
- Lower flue gas temperature giving less natural draft
- Chimney fan or power venter running outside the negative pressure range
- Exhaust gas leaking back into the boiler room
Check in this order
- Consider a variable speed chimney fan or power venter to hold the correct negative pressure.
- Wire a flow proving switch into the boiler LCI circuit.
- Consider a double acting barometric damper or modulating damper to hold negative pressure.
- When any damper is used, install a thermal spill switch to detect exhaust entering the boiler room.
- Check that the thermal spill switch temperature range suits the SlimFit flue gas temperature.
- Set the spill switch point per the system designer and local authority having jurisdiction.
Applies to: Category II vent systems
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit 1000-2000 Series 2 boiler manual, p. 28. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.