Navien · Boiler troubleshooting

Checking vent connections with the Vent Installation Detector (VID)

NCB700

What is going on

The VID helps detect vent pipe separation at the collar, but it does not detect every leak or blockage.

Likely causes

  • Vent pipe pushed out of the collar
  • Leak or disconnect elsewhere in the vent run
  • Blockage of the vent

Check in this order

  1. Insert the vent pipe into the VID to a depth of 2-3/4 in (70 mm); the VID should detect the pipe at this depth.
  2. Inspect all vent pipe connections periodically.
  3. Do not rely on the VID alone to find all vent movement or leaks.

Applies to: Direct vent connections at the boiler collar

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.