Vent system requirements and category selection

SVF

What is going on

The SVF requires a special vent system. Direct exhaust is ANSI Z21.13 Category II (negative pressure vent, condensate likely in vent), with venting detailed on page 29. Direct vent is Category IV (positive pressure vent, condensate likely), with venting detailed on page 38. Vent and air lengths, routing and terminations must follow the limits starting on page 31. Locate the boiler so the vent can be inspected for leaks and deterioration. Replace any existing vent pipes before installing the boiler. Avoid combustion air contamination when using inside air (see page 26).

Check in this order

  1. Choose direct exhaust (Category II) or direct vent (Category IV) and follow the matching section.
  2. Check vent and air lengths, routing and terminations against the limits on page 31 onward.
  3. Locate the boiler so the vent pipes can be inspected.
  4. Inspect and replace any existing vent pipe before installing the boiler.

Applies to: SVF 1500-3000 venting

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 1500-3000 Series 1 boiler manual, p. 9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.