Viessmann · Boiler troubleshooting
Reinstall turbulators and close the boiler
What is going on
Seat the turbulators correctly and close the door evenly.
Check in this order
- On VD2-320 to VD2-860, push the first turbulator element about two thirds into the flue passage, then hook in and push in the second and third elements.
- Tighten the combustion chamber door bolts in a cross pattern. Do not overtighten.
- With a gas power burner, reconnect the gas train and run leak detection tests.
- Reinstall the clean-out opening covers.
Applies to: All VD2 sizes 320 to 1080
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.