Weil-McLain · Boiler troubleshooting
Zoning: WMCR circulator zone controller plus DHW controlled by boiler
What is going on
Zone controller handles space heating. The boiler controls DHW through a direct-piped aquastat.
Check in this order
- Provide relay R1 with a 120 VAC coil and NC contact. Wire it to interrupt the zone controller's ZC-ZR 120 VAC operating circuit so space heating stops during DHW operation.
- Connect the zone controller call for heat (X-X) to INPUT 2 and assign INPUT 2 to PRIORITY 2.
- Connect the DHW aquastat to INPUT 1 and assign INPUT 1 to PRIORITY 1.
- Wire the DHW circulator to OUTPUT 1.
- In the Wizard or the PRIORITY 2 menu, select the matching space heating system type.
- Use the factory DHW defaults or change them as needed.
Applies to: SlimFit Series 3 550/750 with WMCR zone controller
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit Series 3 boiler manual, p. 64. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.