Weil-McLain · Boiler troubleshooting

Zoning: WMCR circulator zone controller plus DHW controlled by boiler

SlimFit Series 3

What is going on

Zone controller handles space heating. The boiler controls DHW through a direct-piped aquastat.

Check in this order

  1. Provide relay R1 with a 120 VAC coil and NC contact. Wire it to interrupt the zone controller's ZC-ZR 120 VAC operating circuit so space heating stops during DHW operation.
  2. Connect the zone controller call for heat (X-X) to INPUT 2 and assign INPUT 2 to PRIORITY 2.
  3. Connect the DHW aquastat to INPUT 1 and assign INPUT 1 to PRIORITY 1.
  4. Wire the DHW circulator to OUTPUT 1.
  5. In the Wizard or the PRIORITY 2 menu, select the matching space heating system type.
  6. Use the factory DHW defaults or change them as needed.

Applies to: SlimFit Series 3 550/750 with WMCR zone controller

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 3 boiler manual, p. 64. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.