Tankless coil hot water goes cold or is always lukewarm

Weil-McLain WTGO Series 4

What is going on

Domestic hot water from the tankless coil runs hot then turns cold, or never gets hot. The coil rating assumes 200°F boiler water.

Likely causes

  • Lime inside the coil
  • Stop-leak compound in the boiler coating the outside of the coil
  • Mixing valve set wrong
  • Hot water flow higher than the coil rating
  • Tankless control set too low or differential too wide

Check in this order

  1. Check the tankless control. To get rated output it should be at 200°F. Lower the differential if it is wide.
  2. Check the mixing valve setting.
  3. Check the hot water flow. If it is above the coil rating, add a flow check valve sized to the coil.
  4. If stop-leak was added to the boiler, remove and clean the coil, then drain and flush the boiler.
  5. If the coil is limed inside, de-lime it or replace it.

Applies to: WTGO-3 to WTGO-9 oil-fired cast iron boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain WTGO Series 4 Boiler Manual 550-142-332/0225, Troubleshooting p.7; System components (tankless heater) p.33. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.