Tankless coil hot water goes cold or is always lukewarm
What is going on
Domestic hot water from the tankless coil runs hot then turns cold, or never gets hot. The coil rating assumes 200°F boiler water.
Likely causes
- Lime inside the coil
- Stop-leak compound in the boiler coating the outside of the coil
- Mixing valve set wrong
- Hot water flow higher than the coil rating
- Tankless control set too low or differential too wide
Check in this order
- Check the tankless control. To get rated output it should be at 200°F. Lower the differential if it is wide.
- Check the mixing valve setting.
- Check the hot water flow. If it is above the coil rating, add a flow check valve sized to the coil.
- If stop-leak was added to the boiler, remove and clean the coil, then drain and flush the boiler.
- If the coil is limed inside, de-lime it or replace it.
Applies to: WTGO-3 to WTGO-9 oil-fired cast iron boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain WTGO Series 4 Boiler Manual 550-142-332/0225, Troubleshooting p.7; System components (tankless heater) p.33. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.