Checking CO2 level at upper heating input
What is going on
Set the burner to maximum output and check CO2 at the flue pipe. Adjust only if outside range.
Check in this order
- Start the burner with the emissions test switch enabled.
- Press button Y or E until the service display shows 100 (100%).
- Check the CO2 level at the flue pipe.
- If adjustment is needed, remove cap B.
- Turn adjusting screw A in small steps with a 3 mm Allen key.
- Turning clockwise lowers CO2 (less gas). Turning counter-clockwise raises CO2 (more gas).
- Record the actual value in the report on page 64.
Applies to: Vitocrossal 200 CM2 186 to 311 boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.