Some radiators do not heat (steam)
What is going on
Part of the steam system stays cold while the boiler runs.
Likely causes
- Main or radiator air vents (one-pipe) or traps (two-pipe) not working
- Pressure limit set wrong
- Clogged piping, valve or radiator
- Radiator valve closed or broken
Check in this order
- Check that each radiator valve is open.
- Check the air vents on one-pipe systems and the traps on two-pipe systems. Repair or replace bad ones.
- Check the pressure limit under 2 psig for most systems, cut-in 1/2 to 1 psi, differential 1 psi.
- Clean or replace clogged pipes, valves or radiators.
Applies to: SGO-3 to SGO-9 oil-fired steam boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Weil-McLain SGO Series 4 Steam Boiler Manual 550-142-330/0825, Troubleshooting p.7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.