Some radiators do not heat (steam)

Weil-McLain SGO Series 4

What is going on

Part of the steam system stays cold while the boiler runs.

Likely causes

  • Main or radiator air vents (one-pipe) or traps (two-pipe) not working
  • Pressure limit set wrong
  • Clogged piping, valve or radiator
  • Radiator valve closed or broken

Check in this order

  1. Check that each radiator valve is open.
  2. Check the air vents on one-pipe systems and the traps on two-pipe systems. Repair or replace bad ones.
  3. Check the pressure limit under 2 psig for most systems, cut-in 1/2 to 1 psi, differential 1 psi.
  4. Clean or replace clogged pipes, valves or radiators.

Applies to: SGO-3 to SGO-9 oil-fired steam boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SGO Series 4 Steam Boiler Manual 550-142-330/0825, Troubleshooting p.7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.