Check remaining appliances on old common vent when removing a boiler
What is going on
Before an SVF boiler replaces an older boiler on a common vent, test each appliance left on that vent, one at a time, to confirm it still vents correctly.
Likely causes
- Removing the old boiler can leave the common vent too large for the remaining appliances
Check in this order
- Seal any unused openings in the common vent.
- Inspect the vent for correct size, horizontal pitch, blockage, restriction, leaks, corrosion or other damage.
- Close building doors, windows and doors to the appliance space.
- Run the clothes dryer, other non-vented appliances and all exhaust fans (except a summer fan) at maximum speed. Close fireplace dampers.
- Make sure no other appliance on the common vent is running. Test one appliance at a time.
- Light the appliance under test and run it continuously for five minutes.
- Check for spillage at the draft hood relief opening using a flame, or smoke from a cigarette, cigar or pipe.
- Return doors, windows, fans, dampers and other appliances to their previous state.
- If the vent does not work correctly, correct it to the National Fuel Gas Code (ANSI Z223.1/NFPA 54), or CAN/CSA B149.1 in Canada. When resizing, use the code tables and approach the minimum size.
Applies to: Replacing an existing boiler on a common vent
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 series 1 boiler manual, p. 32. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.