Weil-McLain · Boiler troubleshooting
High fire and low fire combustion check
What is going on
Check the flame and combustion at both high fire and low fire. Load devices must be able to take the heat so the boiler does not cycle off during adjustment.
Check in this order
- Make sure all load devices (control valves, radiators, air handlers) are running so the boiler does not cycle off.
- Enter Manual Test Mode and call for heat.
- Set FORCE RATE to HIGH. Confirm the maximum firing rate matches Table 18 on page 117.
- Look through the flame inspection window. High fire flame should be blue and stable, with orange dots over the burner surface.
- Remove the test port cap on the vent flue adapter and insert a combustion probe (see Figure 68, page 95).
- Test CO2 and CO against Table 16. If not acceptable, adjust the throttle and offset screws (page 99).
- To check natural gas input run the boiler 10 minutes with other appliances off, time one cubic foot at the meter, and calculate input.
- Set FORCE RATE to LOW. The low fire flame should be stable, uniform orange, and evenly spread over the burner.
- Repeat the combustion test at low fire.
- Set FORCE RATE back to AUTO and press SAVE.
- Reinstall the vent flue cap and confirm it is sealed.
Applies to: SVF 500/600 Series 1 boilers, natural gas and LP
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 Boiler Manual, p. 98-99. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.