Viessmann · Boiler troubleshooting

PP(s) and CPVC vent system limits

Vitocrossal 200 CI2

What is going on

PP(s) vent is flame-retardant polypropylene rated to a maximum of 230 F (110 C) and must be listed to ULC S636 or UL 1738. Do not mix pipe, fittings, or joining methods from different vent makers. CPVC vent must be Type BH Class IIB 90 C.

Check in this order

  1. Confirm PP(s) components are listed to ULC S636 or UL 1738.
  2. Do not mix vent brands, fittings, or joining methods.
  3. For CPVC, use Type BH Class IIB 90 C pipe.
  4. For an existing vent reused with this boiler, seal it so room air cannot be drawn in as combustion air and confirm it is clean and in good condition.
  5. Count the vent and combustion air length in the equivalent length.
  6. If flexible vent or flexible air intake is used, reduce the maximum equivalent length by 25%.

Applies to: PP(s) and CPVC venting

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Installation Instructions, pp. 52-53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.